Digital Process Monitor DPM52A
DPM52A features
DPM52A applications
DPM52A technical parameters
| Parameter | min | nom | max | unit | note |
| Input range | 0 - 20 | mA | |
| Displayed range | -32 768 | | 32 767 | |
| Measuring error | | | 0,3 | % |
| Thermal stability | | | 15 | ppm |
| Long term stability | | | 50 | ppm/1000h |
| Voltage drop on measuring terminals | | | 350 | mV | at 20 mA |
| Maximum measuring terminals current | | | 300 | mA | |
| Analog inputs | 2 | |
| Relay outputs | 2 | |
| Relay outputs form | 1C | |
| Relay output current rating (resistive load) | | | 6 | A | AC |
| Relay output voltage rating | | | 250 | V | AC |
| Samples averaging time (damping) | 0,12 | | 15 | s | parameter |
| Number of averaged samples | 1 | | 125 | | parameter |
| Limit adjustment range | -32 768 | | 32 767 | | parameter |
| Hysteresis adjustment range | 0 | | 32 767 | | parameter |
| Power supply voltage | 18 | 24 | 30 | V | |
| Power supply current | 105 | mA | at 24 V |
| Conductor cross-section for terminals | 0,08 | | 2,5 | mm2 | |
| Dimensions (width x height x depth) | 96 x 48 x 146 | mm |
| Weight | 250 | g |
| Operating ambient temperature | -25 | | 60 | °C |
| Storage ambient temperature | -45 | | 85 | °C |
| Protection | IP20 | |
Download